AC made EZ

Learn how ac drives differ and avoid the guesswork when selecting one for your next design.

An ac motor operating with an open-loop vector drive fully
recovers from the instantaneous application of its full rated load
in 150 msec. Most impressive is that this dynamic response is
accomplished open loop, without the benefit of feedback.

An ac motor operating with an open-loop vector drive fully recovers from the instantaneous application of its full rated load in 150 msec. Most impressive is that this dynamic response is accomplished open loop, without the benefit of feedback.
Select figure to enlarge.

Article Tools

Popular Articles

Motion engineers generally fall into two camps when it comes to ac drive technology: Those already taking advantage of its benefits — low price, compact design, simplicity — and those who will soon start. Both groups, however, face a similar challenge in that they must understand the difference between ac drive types in order to select the right one for a particular job.

In general, ac drives work (controlling ac motor speed) by varying the frequency of the current supplying the motor. Although frequency can be varied many ways, and in relation to other variables such as voltage, the most common methods in use today are “volts per hertz,” open-loop vector, and closed-loop vector. How these techniques differ determines where each drive type works best.

Volts per hertz

Volts per hertz (V/Hz) technology is the most economical and easiest to apply of the three speed-control methods. Here, the drive controls shaft speed by varying the voltage and frequency of the signal powering the motor.

Now, the rotor of an ac induction motor is magnetically coupled to the stator through an induced magnetic field. The speed at which the magnetic field rotates around the stator is known as synchronous speed and is determined by:

n = 120 f/N

where n is synchronous motor speed, 120 is an electrical constant, f is the applied frequency, and N is the number of motor poles.

The equation illustrates one of the basic principles of speed control: Reducing applied frequency to an ac induction motor causes the magnetic field to turn at a proportionally slower rate, thereby reducing rotor speed.

This is only part of the story, however. Induction motors are designed to operate from line voltage at line frequency. But the whole purpose of V/Hz drives is that they don’t hold systems to power line shapes. What they do instead is maintain an optimal voltage-to-frequency ratio, so that the motors they power will produce their rated torque over the widest possible speed range.

Consider a 460-Vac motor designed for 60-Hz operation. If applied frequency is reduced to 30 Hz, the shaft will slow to half its original speed. In this situation, a V/Hz drive also halves the voltage (here, to 230 Vac) in order to maintain the 7.67 V/Hz ratio, which allows the motor to continue producing its rated torque.

Open-loop vector

The design architecture of an open-loop vector drive is similar to that of a V/Hz drive. From a hardware standpoint, the only change is the addition of current sensors. The real difference is in firmware.

Open-loop vector drives use sophisticated motor-control algorithms that independently control both magnetizing and torque-producing current. The algorithms incorporate a detailed motor model that accounts for stator resistance and inductance as well as rated voltage, current, and speed. Using this information, the drive maintains a 90° angle between the magnetizing and torque-producing current vectors.

By independently optimizing magnetizing and torque-producing current, open-loop vector drives significantly raise the level of ac motor performance. Even without a sensor, vector-controlled ac motors will respond quickly to changing load conditions. They also generate more torque and more precisely regulate speed.

Closed-loop vector

Closed-loop vector drives typically incorporate more sophisticated firmware (including the microprocessor) than other drive types. They also require a feedback device (usually an encoder) that’s located on the motor.

By tracking speed and position, closed-loop vector drives are able to accurately control motor torque, speed, and position. Benefits include better speed regulation, full torque production at zero speed, basic positioning, and software-based electronic gearing.

Continue to next page